The HTRC

The Homeowners & Trades Resource Center

You are here: Home / FAQ's, Acronym’s, & Terminology / BS4D: Duct Testing 101

BS4D: Duct Testing 101

duct-testing-new-constructionLately there have been some interesting discussions on exactly what is required for a duct test, especially as it relates to rough in tests & ducts located outside the conditioned envelope. Many of these problems seem to stem with not only a lack of knowledge of what the codes state but also what the standards are (updated 2009-2015 Duct Leakage Chart). As most building departments don’t have enough inspectors, the time for training, or the equipment to do the tests themselves this verification work is generally handled by others.

Who can test?

For many jurisdictions there are 3 generally accepted groups that can do the testing;

  • First off the HVAC contractor may do the verification (generally for only systems they installed & assuming the building department allow it) as long as they have gone through what is called a DET Verifier class. For those taught by Southface, I have no doubt that they were taught properly. Granted many may liken this to the fox guarding the hen house, but if you can’t trust them to do this why did you hire them?
  • The second one allows for certified RESNET Raters (like myself) or HESP to perform the tests which many builders (and even many HVAC contractors) elect to do especially if any code tradeoff calculations are required. As RESNET requires a certain amount of Quality Assurance inspections be done, they are generally pretty careful at getting it done right. With that just like anything else there are bound to be a few bad apples or something I see much more often is ones that don’t stay current.
  • The final batch is where things get a little stickier as many allow any BPI certified individual to do the test. Unfortunately this is an issue as not only are they not tested on this, but never taught about it unless you are going after their Heating Certification or their new specific Duct & Envelope Test Certification (created in late 2014). When it comes down to questionable practices I have seen & heard from some builders, most seem to fall in this camp.

The 4 most common types of tests:

  • The “Total Duct Leakage” or “Post-Construction” test involves sealing up all the registers in the house, hooking up a calibrated fan and pressurizing the duct system to 25 Pascals (Pa). The maximum leakage allowed per the 2012 IECC is 4 CFM per 100 SF of “Conditioned Floor Area” (CFA) while the 2009 IECC allows 12%.
  • The “Rough-In Test” is basically the same as the Total Duct Leakage Test above except this is done before the drywall goes up. The best thing about this test is it allows the contractor to make needed corrections before the finishes are installed and is one of the most popular options. Just like above, the maximum allowed leakage allowed is 4 CFM per 100 SF of “Conditioned Floor Area” under the 2012 IECC while the 2009 allowed for 6%.
  • If the air-handler only is not installed a “Rough-In” test maybe still be completed but all the ducts must be in place including the ones that “bolt onto” the air handler. Under the 2012 codes you are only allowed 3% leakage while the 2009 allowed for 4%. This is one you definetly have to check with the Building Department with as some do not allow this test at all.
  • The “Leakage to Outdoors Test” is a specialty test that requires one to pressurize the house (using a blower door) & duct system (see above) to 25 Pa & measuring how much CFM of is essentially lost outside. This test was allowed under the 2009 IECC (8% leakage) but is not recognized under the 2012 codes. With that many green building programs like ENERGY STAR (unless the system tests at 4% or less) require it along with certain rebate programs like the one offered by NICOR gas in my area.
historyThe RESNET “simplified” standards (quoted below) are used by DET verifiers, Raters, ACCA & other organizations were based off of ASHRAE 152 & the ASTM E1554 standards & protocols. One of the main reasons for the “simplified” standards was their practicality in the field as compared to pretending one worked in a lab. One other big reason is that hardly anyone would pass if they are doing a “Rough In Test” especially if the Air-Handler has not been installed yet. In part this is because they automatically are assessed a penalty of 2.5% of the rated CFM’s to the leakage amount. If both items are missing (register covers & air handler), well it jumps to 5%. So a 3 ton unit automatically has 30/60 CFM of additional leakage which would easily push many over the allowable leakage limits especially if one is dealing with the 2012 codes.

The Codes:

While many claim the codes can be confusing, the codes are pretty clear & simple on what the requirements are. Whether you are following the 2009 or 2012 codes, all joints & seams must be sealed no matter what their location is. Both require testing as we listed above & detail below. The biggest change between the two codes besides the allowable limits is the use of building cavities which the 2012 codes completely ban. Another interesting piece in the 2012 codes is a requirement that the manufacturer of the air handler tighten up their systems which many have already started doing. Below is a copy of the codes taken directly from the code books & only slightly modified for ease of reading (unless reading metric is easier for you).

not-code-compliant-hvac-2012

IRC-20092009: N1103.2.2 Sealing (aka 403.2). Ducts, air handlers, filter boxes and building cavities used as ducts shall be sealed. Joints and seams shall comply with Section M1601.4. Duct tightness shall be verified by either of the following:

1. Post-construction test: Leakage to outdoors shall be less than or equal to 8 CFM per 100 ft2 of CFA or a total leakage less than or equal to 12 CFM per 100 ft2 of CFA when tested at a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer’s air handler end closure. All register boots shall be taped or otherwise sealed during the test.

2. Rough-in test: Total leakage shall be less than or equal to 6 CFM per 100 ft2 of CFA when tested at a pressure differential of 0.1 inch w.g. (25 Pa) across the roughed in system, including the manufacturer’s air handler enclosure. All register boots shall be taped or otherwise sealed during the test. If the air handler is not installed at the time of the test, total leakage shall be less than or equal to 4 CFM per 100 ft2 of CFA.

Exception: Duct tightness test is not required if the air handler and all ducts are located within conditioned space.


2012-iecc2012: R403.2.2 Sealing (Mandatory). Ducts, air handlers, and filter boxes shall be sealed. Joints and seams shall comply with either the International Mechanical Code or International Residential Code, as applicable. Duct tightness shall be verified by either of the following:

1. Post-construction test: Total leakage shall be less than or equal to 4 CFM per 100 SF of CFA when tested at a pressure differential of 0.1     inches w.g. (25 Pa) across the entire system, including the manufacturer’s air handler enclosure. All register boots shall be taped or otherwise sealed during the test.

2. Rough-in test: Total leakage shall be less than or equal to 4 CFM per 100 SF of CFA when tested at a pressure differential of 0.1 inches w.g. (25 Pa) across the system, including the manufacturer’s air handler enclosure. All registers shall be taped or otherwise sealed during the test. If the air handler is not installed at the time of the test, total leakage shall be less than or equal to 3 CFM per 100 SF of CFA.

Exception: The total leakage test is not required for ducts and air handlers located entirely within the building thermal envelope.

R403.2.2.1 Sealed air handler.
Air handlers shall have a manufacturer’s designation for an air leakage of no more than 2 percent of the design air flow rate when tested in     accordance with ASHRAE 193.

R403.2.3 Building cavities (Mandatory).
Building framing cavities shall not be used as ducts or plenums.

Ducts located outside the conditioned envelope:

One of the best things to come out of the required testing of ducts is that many builders started re-evaluating where their ducts are located & they started moving them all inside the conditioned spaces of a building. While one would think that there wouldn’t be any confusion on the terms “entire system” unless “located entirely within the building thermal envelope” or “if the air handler and all ducts are located within conditioned space”… there apparently is. No matter which code book you are using, both require the entire system to be located in conditioned areas or the entire system must be tested, not just the part located outside, or any other definition.

What counts as “Rough In”

This is a picture of a system that was supposedly ready for a “Rough In” test – can you spot the issue?

not-ready-for-duct-test

Well the answer is pretty simple as both tests require that all the duct work be installed including the air-handler enclosure. Ahh but wait, both codes allow for testing without the air-handler being installed, right? While that is true, where is the rest of the duct work that is supposed to be there? Here is a photo of what the completed system looks like with the missing ductwork highlighted.

hvac-system

Additions, Renovations, & oh my:

One of the other big issues that comes up revolves around remodeling projects, system change outs, & additions – just when is a test required. Well for this there is no real easy answer as each building department seemingly has their own take on just what a substantial change is. For example I know some jurisdictions that required testing of the entire system when one changed out just the air handler, while others wouldn’t require it unless 50% or more of the duct work was touched, etc… This is one where you are best talking to the local building department & getting their answer in writing. With that we would strongly recommend that one should test every system & fix it up when given the chance – there is no use putting in a new High Efficient unit where the air doesn’t get where it is really needed – i.e. just like throwing a Porsche engine in a Yugo.

legalRESNET Testing Protocol: aka 803.3 Protocol for Preparing the Building and the Duct System for a Duct Leakage Test

Prep required:

  • 803.3.1 Adjust the HVAC system controls so that the air handler fan does not turn on during the test.
  • 803.3.2 Turn off any fans that could change the pressure in either the conditioned space or any spaces containing ducts or air handlers (bathroom fans, clothes dryers, kitchen vent hood, attic fan, etc.).
  • 803.3.2 Turn off all vented combustion appliances if there is a possibility that the space containing the appliance will be depressurized during the test procedure.
  • 803.3.3 Remove all filters from the duct system and air handler cabinet. If the duct leakage testing system is installed at a central return grille, also remove the filter from that grille.
  • 803.3.4 Any intentional openings into the duct system such as combustion air or ventilation ducts shall be left in their normal non-ventilation operating position. Motorized dampers should be closed.
  • 803.3.5 If ducts run through unconditioned spaces such as attics, garages or crawlspaces, open vents, access panels, doors, or windows between those spaces and the outside to eliminate pressure changes due to duct leakage during the test procedure.
  • 803.3.6 Supply registers and return grilles shall be temporarily sealed in some manner so as to allow for the pressurization of the duct system. — Most use a plastic covering aka Grill Tape while others use a product like Vent Cap systems which many QA providers have started using – for final tests you are not allowed to use foam blocks inside the duct system though ENERGY STAR now does allow for foam to be taped over the opening in carpeted areas only
  • 803.3.7 Zone and bypass (not balancing) dampers shall be set to the open position to allow uniform pressures throughout the duct system.

Total leakage test only: Fully open at least one door, window or comparable opening between the building and outside to prevent changes in building pressure when the duct leakage testing system is running.

Leakage to the outside test only: All exterior doors and windows between the building and outside shall be closed, and other openings to the outside that may hinder the ability of a blower door fan to pressurize the building to 25 Pa with reference to outside should be closed or covered in some manner. Interior doors shall be open.

Equipment setup:

  • 803.4 Installation of the Duct Leakage Testing System (used for both total leakage and leakage to outside tests)
  • 803.4.1 Attach the duct leakage tester system to the largest return grille closest to the air handler. Use the manufacturer’s recommended installation procedure that is consistent with the mode (i.e. pressurization vs. depressurization) of the test being performed. Be sure the remaining opening in the return grille is temporarily sealed. — They do have one exception to this & this is “When testing a duct system with 3 or more returns, installation of the duct leakage tester at the air handler cabinet may be a better attachment location.” This is the one & only time that the air handler is considered an option
  • Document the attachment location of the duct leakage testing system.
  • 803.4.2 Select a location to measure duct pressure. Choose one of the following three locations to measure duct pressure:
    • The largest supply register closest to the air handler, or
    • The main supply trunk line, or
    • The supply plenum can be used if the duct leakage tester is installed at a central return.
    • Document the duct pressure measurement location.
  • 803.4.3 Insert a pressure probe into the duct system at the chosen measurement location. If measuring at the supply trunk line or supply plenum, you must use a static pressure probe (be sure the probe is pointing into the air stream). If measuring at a supply register, you may use a static pressure probe, or you may simply insert a straight pressure probe or the end of a piece of flexible tubing.
  • 803.4.4 Install the pressure gauge and tubing connections in accordance with the manufacturer’s instructions and the test mode (pressurization vs. depressurization) being used. The duct system pressure should be measured with reference to the inside of the building. Turn on and configure the pressure gauge for the test procedure being performed.

Conducting the Test:

  • 803.5 Procedure for Conducting a Total Duct Leakage Test
  • 803.5.1 Select the appropriate range (e.g. flow ring) of the duct leakage testing fan and configure the flow gauge to match the selected range.
  • 803.5.2 Turn on the duct leakage testing fan and increase fan speed until the duct system has been pressurized to 25 Pa (+/- 0.5 Pa). Measure and record the duct pressure reading (0.1 Pa resolution) and the fan flow reading (1 CFM resolution) using a 5 second averaging period. Also record the fan configuration (range), fan and manometer models and serial numbers. Be sure the fan is being operated according to the manufacturer’s instructions.
    • If 25 Pa of duct pressure cannot be achieved because the duct testing fan does not have sufficient flow capacity, then achieve the     highest duct pressure possible with the equipment available and record the values above.
    • Note: If your pressure gauge has the capability to adjust the fan flow value to a duct pressure of 25 Pa (i.e. @25 Pa feature), then follow the manufacturer’s procedures for conducting a one-point total leakage test, and record the following values: duct pressure, CFM25 (or fan flow in CFM and pressure in Pa if 25 Pa not achieved), fan configuration, fan and manometer models and serial numbers. If your gauge does not have an @25 feature and the measured duct pressure was not exactly 25 Pa, calculate and record CFM25 as: CFM25 = (25 Pa/ duct pressure)0.6 x fan flow.
  • 803.5.3 Turn off the duct testing fan.

Related posts:

Who & what is NARI and this Code of Ethics you mention?

Gas vs Diesel vs Electric: Trucks, SUV's, Towing & Camping

FAQ: Where should I place a Stand-Alone Freezer?

Know Thy Numbers: Ice & Water Shield / Barrier

Say what… aka the acronym dilemma

FAQ: Should I always use the Bathroom Fan when taking a Shower?

FAQ: Does my freezer really need to be kept at 0º?

FAQ: What decking material should I use

Tweet

Filed Under: FAQ's, Acronym’s, & Terminology November 15, 2013 By SLS

Popular Categories

  • Common Sense Building
  • Tips & Tricks
  • FAQ’s, Acronym’s, & Terminology
  • Off-Grid Living
  • Spring Maintenance Checklist
  • Air Sealing & Insulation
  • Building Codes
  • Disaster Preparation
  • Deck & Outdoor Living
  • Holiday & Vacations
  • How-To’s & Planners
  • Myth or Misconception
  • Tool & Shop Safety
  • Universal Design

The HTRC - Copyright © 2006–2025 by TheHTRC.com & SLS Construction & Building Solutions LLC http://SLS-Construction.com